![]() as appropriate) tend to use as a guide when enacting local electrical codes. The NEC is not any jurisdiction's electrical code per se rather, it is an influential work of standards that local legislators (e.g., city council members, state legislators, etc. The purpose of the NEC is to protect persons and property from hazards arising from the use of electricity. Governments cannot distribute the NEC itself for copyright reasons, though parts that have been adopted into law are not subject to copyright. Local jurisdictions usually adopt the NEC or another published code and then distribute documents describing how local codes vary from the published codes. It is sponsored by the National Fire Protection Association (NFPA) and has been periodically revised since 1897. The National Electrical Code (NEC) specifies minimum acceptable wiring methods and materials for many states and municipalities in the U.S. Ordinary switches control but do not consume electricity, and therefore are not defined as outlets in this sense. This definition includes receptacles, lighting, motors, etc. An outlet is defined by the NEC as "a point in the wiring system at which current is taken to utilization equipment".For larger commercial installations, 277/480 V or 347/600 V three phase is common. The third phase, the "high leg" of the system (also referred to as the "wild leg"), has 208 V to neutral and is not usually used for single-phase connections, so is distinctively colored. An older, but still widely used high-leg delta system uses three phases with 240 volts phase-to-phase for motor loads, and 120 volts for lighting loads by use of a center-tapped transformer two of the phases are 120 volts to neutral. The most common three-phase system will have three hot legs, 208 V to each other and 120 V each to the neutral. The most common residential and small commercial service in Canada and the U.S., single split-phase, 240 V, features a neutral and two hot legs, 240 V to each other, and 120 V each to the neutral. Leg as in "hot leg" refers to one of multiple hot conductors in an electrical system.It is either bare or has green insulation. ![]() It is often called the "ground wire," or safety ground. Ground is a safety conductor with a low impedance path to earth.Hot is any line or neutral conductor (wire or otherwise) connected with an electrical system that has electric potential relative to electrical ground or line to neutral. ![]() ![]() Formally, the neutral is called the "grounded conductor" as of the 2008 NEC, the terms "neutral conductor" and "neutral point" have been defined in the Code to conform to what had been common usage. United States electrical codes require that the neutral be connected to earth at the "service panel" only and at no other point within the building wiring system. The neutral is connected to the center tap of the power company transformer of a split-phase system, or the center of the wye connection of a polyphase power system. North American standards state that the neutral is neither switched nor fused except in very narrowly defined circumstances.
0 Comments
Leave a Reply. |
AuthorWrite something about yourself. No need to be fancy, just an overview. ArchivesCategories |